LSS type vertical automatic steam generator without inspection has simple and accurate control technology, high thermal efficiency, short preheating time, and adopts arc-shaped tube structure to make the heat and cold exchange uniform and reach the set pressure at a higher speed. The steam pressure can reach 0.4mpa within 5-8 minutes after starting up. It is controlled by a one-key start button, and up to 4 time periods can be set to automatically start up and run. The equipment is equipped with multiple protection measures such as automatic water filling, pressure control, water shortage protection and alarm, automatic shutdown of extremely low water level, overpressure protection, and overpressure safety valve.
Technical Parameters
Model | LSS0.1-0.4-Y | LSS0.2-0.4-Y | LSS0.3-0.4-Y(Q) | LSS0.5-0.4-Y(Q) | LSS0.7-0.4-Y(Q) | LSS1-0.7-Y(Q) | |||
(Q) | (Q) | LSS0.3-0.7-Y(Q) | LSS0.5-0.7-Y(Q) | LSS0.7-0.7-Y(Q) | LSS1-1.0-Y(Q) | ||||
Rated steam capacity(t/h) | 0.1 | 0.2 | 0.3 | 0.5 | 0.7 | 1 | |||
Rated steam pressure(Mpa) | 0.4 | 0.4 | 0.4/0.7 | 0.4/0.7 | 0.4/0.7 | 0.7/1.0 | |||
Steam temperature(C) | 151 | 151 | 151/170 | 151/170 | 151/170 | 170/184 | |||
Supply water temperature(C) | 20 | 20 | 20 | 20 | 20 | 20 | |||
Thermal efficiency(%) | 89 | 89.2 | 90.6 | 90.6 | 93.9 | 92 | |||
Fuel available | Light diesel oil, heavy oil, natural gas | ||||||||
Motor General power(kw) | 1.1 | 2.6 | 2.66 | 2.96 | 3.2 | 4 | |||
Fuel consumption | Light oil (Kg/h) | 6.6 | 14 | 20.62 | 34.37 | 46.53 | 67.88 | ||
Natural gas (Nm³/h) | 9 | 19 | 24.98 | 41.69 | 56.22 | 82.61 | |||
Boiler weight(t) | 0.83 | 1 | 2.113 | 2.657 | 3.64 | 3.75/3.9 | |||
Boiler size(m)(L×W×H) | 0.8×1.94 | 0.9×2.7 | 1340×1300×2510 | 1540×1500×2860 | 1900×1800×3040 | 1900×1800×3310 | |||
Note: 1. The hot value of light oil: 10300kal/Nm3, hot value of natural gas :8500kcal/Nm3. | |||||||||
2. Parameter is for reference only, if any changes should follow actual drawings. |
Boiler Features
1.The small water volume, fast steam generating. LHS Series steam boiler has vertical design and compact structure, just requires small floor space;
2.Adopting large-volume steam chamber, and lay-in steam/water separator can produce high-quality steam stably;
3.The lay-in low water level protection device to detect the change of water level at any time, totally avoid dry-burning and operation accidents;
4.LSS Series vertical type steam boiler is equipped with high-quality pressure relief valve, water level electrode, water level gauge, pressure gauge, pressure controller, and other accessories to ensure boiler’s reliable operation.
Boiler Application
LSS series vertical steam generator can be wildly used in pharmaceutical industry, chemical industry, light industry, textile, building materials, farming, food and beverage, plastics and foam, printing & dyeing and washing, rubber processing, paper making, wood processing, hotel, garment leather, etc. This series boiler can also be applied to generate electricity at some districts where electricity power is in short. Even they can be used as a power plant boiler start-up.